Walk In Cooler Evaporator Placement: Plan the Airflow First

Ceiling mounted evaporator coil with two fans on the short wall of an empty walk in cooler, with airflow arrows over wire shelving

Where should the walk in cooler evaporator go? In many rooms the answer is decided by whichever wall is left after the shelving has been drawn. The room then spends years with a cold corner, a warm corner and frost on the boxes nearest the coil. The evaporator is the part of the system that takes heat out of the room, and its position decides how air moves around your stock. This guide covers which wall to choose, how the coil relates to the door and shelving, and the drain and service access it needs.

The coil is where the room gives up its heat

Inside the room, a fan pushes air through the evaporator coil, where refrigerant absorbs heat from it. The cooled air leaves the face of the coil, travels across the ceiling, drops along the far wall and works its way back to the coil through the stock. Anything that blocks that loop, such as cases stacked to the ceiling or a shelf right under the coil, leaves part of the room warmer than the display suggests. NRCan guidance describes the evaporator fan coil as usually mounted on the room's ceiling, with the compressor usually mounted outside the room.

Titan installs a complete refrigeration system with every walk in it designs, builds or relocates, including the condensing unit, evaporator and controls. That matters for placement, because the coil is chosen and positioned with the box rather than added afterwards. Some products also need gentle air. For meat rooms, we plan gentle airflow that protects the product. In rooms like that, the coil and its air speed should suit the product as well as the room size.

Pick the coil wall before you pick the shelving

In a rectangular room, the coil generally works best on a short wall, blowing along the length of the room so the air has a clear run to the far end. Hanging it on a long wall can leave the ends of the room poorly served. Keep the coil away from the area right above the door if you can, because warm, damp air enters every time the door opens and a coil that draws that air in straight away can frost faster.

Then draw the shelving around the airflow. Leave clear space in front of the coil face and below it, keep the top shelf below the path of the air, and avoid solid shelf backs on the wall opposite the coil that would stop the air dropping down. Plan the aisle spacing for stock rotation at the same time, so the aisles and the airflow work together rather than against each other.

The door and the coil should not work against each other

Every door opening lets warm air in, and the coil has to deal with that air and its moisture. A coil that blows straight at the door can push cold air out of the opening and pull warm air in behind it. Positioning the coil so its air runs along the room rather than towards the doorway reduces that exchange. In busy rooms, door habits matter too: a door that closes reliably, a strip curtain where it suits the traffic and staff who pull stock in one trip all reduce the load on the coil.

Fan behaviour belongs in the same plan. In many coolers the fans run continuously to keep air moving, but NRCan guidance mentions evaporator fan control that can run fans at variable speed, or cycle them on and off, while the compressor is off. Ask which approach suits your product before the controls are set.

If the room serves a display wall or a kitchen line with frequent openings, raise placement early with the designer. Our walk in cooler installation process treats the coil, the condensing unit and the lines between them as one job. On our installations, the evaporator, condensing unit and refrigerant lines are installed and pressure tested.

Drain, service access and the space above the coil

The coil produces water as it removes moisture from the air, and that water needs a drain line with a steady fall to a suitable drain. In a freezer the line usually needs heat so it does not freeze. Plan the drain route at the same time as the coil wall, because a coil on the far side of the room from any drain means a long line running across the ceiling or floor.

Leave room to work. A technician needs to reach the fan motors, the coil face and the drain pan without unloading half the room. Shelving tight under the coil, or a coil tucked into a corner behind a column, makes routine cleaning harder and tends to delay it.

Operator's refrigeration decision: draw the airflow before the shelving

Coil placement is cheap to get right on paper and disruptive to change once the room is stocked. Decide the coil wall, the door position and the shelving together, check the drain route, and leave service space. Refrigeration is installed as part of every cooler and freezer we design, build or relocate across the GTA and Southern Ontario. Operators in Toronto can see how we plan rooms on our Toronto cooler and freezer page, and operators in Hamilton can find local details on our Hamilton cooler page.